logo资料库

SMC-PLUS 软启动器使用手册.pdf

第1页 / 共25页
第2页 / 共25页
第3页 / 共25页
第4页 / 共25页
第5页 / 共25页
第6页 / 共25页
第7页 / 共25页
第8页 / 共25页
资料共25页,剩余部分请下载后查看
Pub. Number/Date
1 - Catalog Number Identification
2 - Installation and Wiring
Inspection
Ventilated Enclosures
Non-ventilated Enclosures
Mounting
Control Power
Fan Power
Typical Connection
Typical Connection with Isolation Contactor
Typical Connection for Retrofit Application
By-Pass Mode
Typical Connection with Shunt Trip Circuit Breaker
Programmable Controller and Sensor Interface
Power Factor Capacitors
Fast Acting Current-limiting Fuses
Motor Overload Protection
Protective Module
3 - Set-up Procedures: SMP PLUS Controller without Options
Protective Features
Start Fault
Stalled Motor
Temperature Fault
Line Fault
Factory Settings
Start Sequence
Normal Stop Sequence
Overload Trips
Fault Trips
Customer Settings
Soft Start
Soft Start with Kickstart
Soft Start Selection without Options
Current Limit Start Selection without Options
Full Voltage Starting
Full Voltage Start Selection without Options
4 - Troubleshooting
Control Module Removal
Power Module Resistance Check
Renewal Parts
This manual describes the installation, setup, operation and use of the SMC PLUS Controller. Basic installation and troubleshooting instructions apply to all of the SMC PLUS Controllers. The wiring and set-up procedures are for the SMC PLUS Controllers without options only. Wiring and set-up procedures fo the SMC PLUS Controllers with options can be found in the following publications: • • • • • • 150-805 Soft Stop Option 150-806 Pump Control Option 150-807 Preset Slow Speed 150-808 SMBTM Smart Motor Braking 150-809 Accu-StopTM Option 150-810 Slow Speed with Braking
Chapter 1 Catalog Number Identification The following is an explanation of the catalog numbering system for the Bulletin 150 SMC PLUS Smart Motor Controller. Catalog Number Identification Figure 1.1 – Open Type Controllers Figure 1.2 – Combination Controllers 150 – A24 N BD A – 8L4 152H – W A 39–B A– Bulletin Number 152H Combination Controller with fusible disconnect and isolation contactor 152B Combination Controller with fusible disconnect 153H Combination Controller with circuit breaker and isolation contactor 153B Combination Controller with circuit breaker Controller Rating W Z Standard duty Heavy duty Type of Enclosure A J NEMA1 B NEMA 1 Vent. NEMA12 Voltage Rating H A B C 200 volts, 50/60 Hz 240 volts, 50/60 Hz 480 volts, 50/60 Hz 600 volts, 50/60 Hz HP Horsepower Cat. No. Rating 39 40 41 42 43 44 45 46 5 7.5 10 15 20 25 30 40 HP Cat. No. Rating 47 48 49 50 51 52 54 56 50 60 75 100 125 150 200 250 HP Cat. No. Rating 57 58 59 60 61 62 63 300 350 400 450 500 600 700 Options (only one option may be added to standard unit) A B C D E F Soft Stop Pump Control Preset Slow Speed SMB Smart Motor Braking Accu-Stop Slow Speed with Braking Bulletin Number 150 Solid–State Controller Controller Rating A24 24 amperes (standard duty) 1–15 hp @ 480V 21 amperes (heavy duty) 1–15 hp @ 480V 35 amperes (standard duty) 1–25 hp @ 480V 30 amperes (heavy duty) 1–20 hp @ 480V 54 amperes (standard duty) 1–40 hp @ 480V 45 amperes (heavy duty) 1–30 hp @ 480V 97 amperes (standard duty) 5–75 hp @ 480V 79 amperes (heavy duty) 5–60 hp @ 480V A35 A54 A97 A135 135 amperes (standard duty) 5–100 hp @ 480V 105 amperes (heavy duty) 5–75 hp @ 480V Type of Enclosure N A Open NEMA 1 B NEMA 1 Vent. Input Line Voltage BD CD 200–480 volts, 3–phase, 50 and 60 Hz 200–600 volts, 3–phase, 50 and 60 Hz Options Functions (Only one option may be added to standard unit) A B C Soft Stop Pump Control Preset Slow Speed SMB Smart Motor Braking Accu–Stop Slow Speed with Braking D E F Options 8L4 Max. 480 volt, line mounted Protective Module 8L6 Max. 600 volt, line mounted Protective Module 8M4 Max. 480 volt, load mounted Protective Module 8M6 Max. 600 volt, load mounted Protective Module 8B4 Max. 480 volt, line and load mounted Protective Module 8B6 Max. 600 volt, line and load mounted Protective Module Accessories for Field Mounting Protective Module – • For 24A, 35A, and 54A controllers: 150-N84 150-N86 Protective Module (max. 480V) Protective Module (max. 600V) • For 97A–135A controller: 150-N84L 150-N86L 150-NT1 199-LF1 Protective Module with wire leads (max. 480V) Protective Module with wire leads (max. 600V) IEC line and load terminal cover Terminal Lug Kit
1-2 Chapter 1 Catalog Number Identification Specifications • Input Voltage – Power Module: – 200 – 480 VAC, 3–phase, +10%, –15% – 200 – 600 VAC, 3–phase, +10%, –15% • Control Voltage – Control Module: 100 – 240 VAC, 1 phase, +10%, –15% • Input Frequency – Control and Power: 50 and 60 Hz • Repetitive Peak Inverse Voltage Rating: – 1400V (Line voltage 200–480V) – 1600V (Line voltage 200–600V) • Operating Temperature: 0°C to +50°C • Storage Temperature: –40°C to +85°C • Relative Humidity: 5 – 95% (non–condensing) • Shock: 30 G shock peak acceleration for 11 ms Standard Adjustments • Soft Start: – 2 to 30 seconds • Initial Torque: – 5 to 90% locked rotor torque • Kickstart: – 500% current for 0.4 to 2 seconds • Current Limit: – 50 to 500% full load amperes • Vibration: 2.5 G vibration for 60 minutes • Altitude: 2000 meters without derating • Noise and RF Immunity: Surge transient 3KV peak, 1500 V showering arc • Auxiliary Contact Rating: – N.O.– 470 VA sealed, 4700 VA inrush, 240V max., 24V min. – N.C.– 275 VA sealed, 2750 VA inrush, 240V max., 24V min. • Diagnostics: – Start Fault – Stalled Motor – Temperature Fault – Line Fault • DV/DT Protection: RC Snubber Network • Transient Protection (optional): Metal Oxide Varistors, 220 joules Options • Soft Stop: – 2 to 60 seconds • Preset Slow Speed: – Forward: 7% (LOW) or 15% (HIGH) speed – Reverse: 10% (LOW) or 20% (HIGH) speed – Slow Speed Current adjustment (50 to 450% of full load current) • Pump Control: – Starting: 2 to 30 seconds – Stopping: 2 to 120 seconds • SMB Smart Motor Brake: – Braking Current 150 to 400% full load amperes • Accu-Stop – Slow Speed:7% (LOW) and 15% (HIGH) – Slow Speed Current adjustment (50 to 450% of full load current) – Braking Current (150 to 400% full load current) • Slow Speed with Braking – Slow Speed: 7% (LOW) and 15% (HIGH) – Slow Speed Current adjustment (50 to 450% of full load current) – Braking Current (150 to 400% full load current) – Slow Speed Acceleration Current Adjustment (50 to 400% of full load current)
Chapter 2 Installation and Wiring Inspection Before installing the controller, make a complete visual check of the controller for damage in shipment or handling. Claims for damaged or missing parts must be made to the carrier as soon as possible after receipt of shipment. Enclosures The open-style controller can be installed in an enclosure. The internal temperature of the enclosure must be kept within the range of 0°C to 50°C. Ventilated Enclosures For NEMA Type 1 enclosures, the following guidelines are recommended in order to limit the maximum controller ambient temperature. There should be a clearance of at least six inches above and below the controller. This area allows air to flow through the heatsink. Ventilation openings are required above and below this air space. An outlet should be placed at least six inches above the controller. The inlet should be placed near the bottom of the enclosure. It should be capable of accepting a fan rated 110 CFM or greater. A filter is required to prevent contaminants from entering the enclosure. The minimum vent area should be ten square inches. For the 97 and 135 amp controller, the minimum vent area should be 36 square inches. Deductions must be made for the grill work or ventilation pattern. CAUTION: When thermal overload relays are installed in the same enclosure, a barrier should be provided around the relay. However, this should not inhibit air flow on forced air cooled units (97 and 135A). ! The following table shows the maximum heat dissipation at rated current for the controllers. For currents lower than rated value, heat dissipation will be lower. Figure 2.1 - Maximum Heat Dissipation SMC PLUS Controller Current Size Maximum Watts 24A 110 35A 150 54A 200 97A 285 135A 410 Non-ventilated Enclosures For NEMA Type 12 or non-ventilated enclosures, it is recommended that a by-pass contactor be used. This will allow the controller to start the motor. Once up to full voltage, the controller would be by-passed. Note that the energy saver and protective features of the controller would no longer be available. See Page 2-5, Figure 2.10 for this configuration. Mounting The controller is convection cooled except for the 97A and 135A fan cooled unit. It is important to locate the controller in a position which allows free air flow vertically through the power module. The controller must be mounted with heatsink fins in a vertical plane and have a minimum of 6 inches free space above and below the controller. See Figure 2.2.
2-2 Chapter 2 Installation and Wiring Figure 2.2 - Dimension Drawings 24, 35, and 54 Amp Controller 97 and 135 Amp Controller C D A E A E C D H J B F G Unit Millimeter Inch Millimeter Inch A Width 154 6-1/16 214 8-7/16 B Height 180 7-3/32 240 .281 DIA. (04.14) 4 Mtg. Holes .219 DIA. (05.56) 4 Mtg. Holes G F B .281 DIA. (04.14) 4 Mtg. Holes C Depth 159 D 50 E 140 F 160 G 140 H 10 J 20 6-17/64 1-31/32 5-33/64 6-5/16 5-33/64 13/32 51/64 169 60 9-29/64 6-21/32 2-23/64 200 7-7/8 230 200 7-7/8 240 180 20 30 7-3/32 51/64 1-3/16 200 7-7/8 25 45 63/64 1-25/32 Millimeter 244 290 199 90 Inch 9-39/64 11-27/64 7-27/32 3-35/64 9-1/64 9-29/64 Millimeter 248 336 230 128 220 250 40 Inch 9-49/64 13-15/64 9-1/16 5-3/64 8-21/32 9-27/32 1-39/64 Approx. Ship. Wt. 4.5 kg 10 lbs 6.8 kg 15 lbs 11.3 kg 25 lbs 10.4 kg (97A) 11.8 kg (135A) 23 lbs (97A) 26 lbs (135A) 24A 24A Controller 35A 35A Controller 54A 54A Controller 97A and and 35A Controllers All dimensions are approximate and are not to be used for construction purposes. Refer to nearest Sales Office or the Sales Department at Milwaukee, Wisconsin, for complete dimension drawings. Figure 2.3 - Wiring Terminal Locations Wiring Input Connections Control Circuit Connections Output Connections The controller wiring terminal locations are shown in Figure 2.3. Make wiring connections as indicated in the typical connection diagrams shown in Figures 2.7, 2.8, 2.9, 2.10, and 2.11. Connect the line to terminals L1/1, L2/3, and L3/5. Connect the load to terminals T1/2, T2/4, and T3/6. A provision is available for grounding the isolated heatsink per applicable codes.
Chapter 2 Installation & Wiring Figure 2.4 - Power Wiring and Power Lug Connections 2-3 Controller Controller 24 A-54 A 97 A-135 A Wire Size Metric 2.5 - 25 mm2 16 - 120 mm2 AWG #14 – #4 6 – 4/0 Tightening Torque Wiring Size Wiring Size Torque Torque 2.5-6 mm2 14–10 AWG 2.80 N-m 25 LB-IN 10 mm2 8 AWG 3.4 N-m 30 LB-IN 16-25 mm2 6–4 AWG 3.95 N-m 35 LB-IN 16-120 mm2 6 – 4/0 31 N-m 275 LB-IN Control Power Control voltage: 100–240 VAC, (+10/–15%), 1 phase, 50/60 Hz. Connect control power to the controller at terminals 10 and 60. The control power requirement is 30 VA. In addition, 45 VA capacity is required to operate the heatsink fan on the 97 and 135 Amp controller. Additional control circuit transformer VA capacity may be required depending on the specific application. Use the following figure as a guide for control wiring: Figure 2.5 - Control Wiring and Tightening Torque Metric AWG Wire Size 1.5 - 4 mm2 #14 – #12 Torque 3.95 N-m 35 LB-IN The wiring of the control circuit depends on the specific application. Typical connections for a number of typical applications are shown in Figures 2.7 through 2.12. Fan Power The 97 and 135 Amp controllers have a heatsink fan which requires an additional 45VA capacity. To gain access to the fan connection, see Figure 2.6. CAUTION: The fan jumpers have been factory installed for 110/120 VAC input. Refer to Figure 2.6 for optional 220/240 VAC fan wiring. After control wiring is complete, replace control terminal strip cover. ! NOTE: Jumpers have been factory installed for 110/120 VAC input. Figure 2.6 - Location of Fan Wiring and Jumpers for 97A and 135A Controller Factory Set 110/120 VAC Fan Power Optional 220/240 VAC Fan Power 11 12 13 14 Jumpers To Supply 11 12 13 14 To Supply Jumpers NOTE: Customer is to wire fan to control voltage supply. Jumpers are factory arranged for 110/120 VAC fan power.
2-4 Chapter 2 Installation and Wiring Typical Connection Figure 2.7 shows a typical connection for standard control module. See page 3-2 for a description of the start sequence. Figure 2.7 - Typical Connection Diagram for Standard Unit NOTE: For two wire control, remove stop/start push buttons and connect two wire device between terminals 10 and 40. Customer Supplied ` Customer wires fan to control voltage supply. Jumpers are arranged for 110/120 VAC fan power. Power Input 3-Phase To Supply Jumper 11 12 13 14 Optional 220/240 VAC Fan Power Overload Relay SMC PLUS Controller L1/1 T1/2 L2/3 T2/4 L3/5 T3/6 M Fast-Acting SCR fuses (optional) Branch Protection Jumper 11 12 13 14 Stop Start Fan Power (97A and 135A Only) ` O.L. 10 20 30 40 50 60 70 80 90 Auxiliary Contacts SMC PLUS Control Terminals Typical Connection with Isolation Contactor Figure 2.8 shows a typical connection of standard unit for use with an isolation contactor. Starting and stopping of the motor is controlled by the controller. The controller also controls the electromechanical contactor. The contactor provides isolation between the motor and the power lines when the controller is “OFF.” ! WARNING: When not using an isolation contactor, hazardous voltages are present at the load terminals of the controller when the controller is turned off. Warning labels must be attached to the motor terminal box, the controller enclosure, and the control station. Additional circuitry must be included to provide automatic isolation. Figure 2.8 - Typical Connection Diagram of Standard Unit with Isolation Contactor NOTE: For two wire control, remove stop/start push buttons and connect two wire device between terminals 10 and 40. Power Input 3-Phase Customer Supplied ` Customer wires fan to control voltage supply. Jumpers are arranged for 110/120 VAC fan power. ´ Set auxiliary contact for normal setting. L1/1 T1/2 L2/3 T2/4 L3/5 T3/6 M Branch Protection Fast-Acting SCR fuses (optional) SMC PLUS Controller To Supply Jumper 11 12 13 14 Optional 220/240 VAC Fan Power Jumper 11 12 13 14 Fan Power (97A and 135A Only) ` C.I. Stop Start O.L. 10 20 30 40 50 60 70 80 90 SMC PLUS Control Terminals Auxiliary Contacts ´
分享到:
收藏