Contents
1 Parameters
1.1 Introduction to Parameters
1.2 List of Parameters
r0000 Drive display / Drive display
r0002 Drive state / Drive state
r0002 Drive state / Drive state
p0003 User access level / User access level
p0004 Parameter filter / Parameter filter
p0004 Parameter filter / Parameter filter
p0005[0...2] Display selection / Display selection
p0006 Display mode / Display mode
p0007 Backlight delay time / Backl. delay time
p0010 Commissioning parameter / Commissioning par.
p0010 Commissioning parameter / Commissioning par.
p0011 Lock for user defined parameter / LockUserDefinedPar
p0012 Key for user defined parameter / Key UserDefinedPar
p0013[0...19] User defined parameter / Userdefined par
p0014[0...2] Store mode / Store mode
r0018 Firmware version / Firmware version
r0019.0...14 CO/BO: BOP control word / BOP CtrlWd
r0020 CO: Freq. setpoint before RFG / Setp before RFG
r0021 CO: Act. filtered frequency / Act. filt. freq.
r0022 Act. filtered rotor speed / Act fil rotorspeed
r0024 CO: Act. filt. output frequency / Act. outp. freq
r0025 CO: Act. output voltage / Act.outp. volt
r0026[0...1] CO: Act. filtered DC-link volt. / Act. fil. Vdc
r0027 CO: Act. output current / Act. outp. cur
r0029 CO: Flux gen. current / Flux gen. cur.
r0030 CO: Torque gen. current / Torque gen.cur
r0031 CO: Act. filtered torque / Act fil torque
r0032 CO: Act. filtered power / Act fil. power
r0035[0...2] CO: Act. motor temperature / Act. mot.temp.
r0036 CO: Inverter overload utilization / Invert ovl util
r0037[0...1] CO: Inverter temperature [C] / Inverter temp.
r0038 CO: Fil. power factor / Fil.power fact
r0039 CO: Energy consumpt. meter [kWh] / Energy meter
p0040 Reset energy consumption meter / Reset energy meter
r0050 CO/BO: Active Command Dataset / Active CDS
r0051[0...1] CO: Active Drive Dataset (DDS) / Active DDS
r0052.0...15 CO/BO: Act. status word 1 / Act StatWd1
r0053.0...15 CO/BO: Act. status word 2 / Act StatWd2
r0053.1...15 CO/BO: Act. status word 2 / Act StatWd2
r0054.0...15 CO/BO: Act. control word 1 / Act CtrlWd1
r0055.0...15 CO/BO: Act. control word 2 / Act CtrlWd2
r0055.0...15 CO/BO: Act. control word 2 / Act CtrlWd2
r0056.0...15 CO/BO: Status of motor control / Stat MotCtrl
r0056.0...13 CO/BO: Status of motor control / Stat MotCtrl
r0061 CO: Act. rotor speed / Act rotor speed
r0062 CO: Freq. setpoint / Freq. setpoint
r0063 CO: Act. frequency / Act. frequency
r0063 CO: Act. frequency / Act. frequency
r0064 CO: Dev. frequency controller / Dev. freq ctrl
r0065 CO: Slip frequency / Slip frequency
r0066 CO: Act. output frequency / Act. outp freq
r0067 CO: Act. output current limit / Outp cur limit
r0067 CO: Act. output current limit / Outp cur limit
r0068 CO: Output current / Output current
r0069[0...5] CO: Act. phase currents / Act. phase cur
r0070 CO: Act. DC-link voltage / Act. Vdc
r0071 CO: Max. output voltage / Max. outp.volt
r0072 CO: Act. output voltage / Act. outp.volt
r0074 CO: Act. modulation / Act modulation
r0075 CO: Current setpoint Isd / Cur. setp. Isd
r0076 CO: Act. current Isd / Act. cur. Isd
r0077 CO: Current setpoint Isq / Cur. setp. Isq
r0078 CO: Act. current Isq / Act. cur. Isq
r0079 CO: Torque setpoint (total) / Total trq setp
r0080 CO: Act. torque / Act. torque
r0084 CO: Act. air gap flux / Air gap flux
r0085 CO: Act. re-active current / Act.reactive cur
r0086 CO: Act. active current / Act.active cur
r0087 CO: Act. power factor / Act.power fact
r0090 CO: Act. rotor angle / Act rotor angle
r0094 CO: Transformation angle / Transf. angle
p0095[0...9] CI: Display PZD signals / PZD signals
r0096[0...9] PZD signals / PZD signals
p0100 Europe / North America / Europe / Nth Amer.
r0191[0...2] Configuration Control Unit / Config CU
p0199 Equipment system number / Equip. system no.
p0201[0...2] Act. power module code number / Act.Pmod. code no
r0203 Act. inverter type / Act. inverter type
r0204 Power module features / Pmodule features
r0204 Power module features / Pmodule features
p0205 Inverter application / Inverter appl.
r0206 Rated inverter power [kW] / [hp] / Rated power[kW/hp]
r0207[0...2] Rated inverter current / Rated inverter cur
r0208 Rated inverter voltage / Rated voltage
r0209 Maximum inverter current / Max. inverter cur
p0210 Supply voltage / Supply voltage
p0230 Output filter / Output filter
r0231[0...1] Max. cable length / Max. cable length
p0233 Filter inductance / Filter inductance
p0234 Filter capacity / Filter capacity
p0290 Inverter overload reaction / Overload reaction
p0291[0...2] Inverter protection / Inverter protect.
p0292 Inverter temperature warning / Inv. temp. warn.
p0294 Inverter I2t warning / Inv. I2t warn.
p0295 Inverter fan off delay time / Fan delay time
p0300[0...2] Select motor type / Select motor type
p0300[0...2] Select motor type / Select motor type
p0304[0...2] Rated motor voltage / Rated mot. voltage
p0305[0...2] Rated motor current / Rated mot. current
p0307[0...2] Rated motor power / Rated motor power
p0308[0...2] Rated motor cosPhi / Rated mot. cosPhi
p0309[0...2] Rated motor efficiency / Rated efficiency
p0310[0...2] Rated motor frequency / Rated motor freq.
p0311[0...2] Rated motor speed / Rated motor speed
r0313[0...2] Motor pole pairs / Motor pole pairs
p0314[0...2] Motor pole pair number / Motor pole pair no
p0320[0...2] Motor magnetizing current / Motor magnet. cur.
r0330[0...2] Rated motor slip / Rated motor slip
r0331[0...2] Rated magnetization current / Rated magnet. cur.
r0332[0...2] Rated power factor / Rated power factor
r0333[0...2] Rated motor torque / Rated motor torque
p0335[0...2] Motor cooling / Motor cooling
p0340[0...2] Calculation of motor parameters / Calc of mot.params
p0341[0...2] Motor inertia [kg*m^2] / Inertia [kg*m^2]
p0342[0...2] Total/motor inertia ratio / Tot/mot inert.rat.
p0344[0...2] Motor weight / Motor weight
r0345[0...2] Motor start-up time / Mot. startup time
p0346[0...2] Magnetization time / Magnetization time
p0347[0...2] Demagnetization time / Demagnet. time
p0350[0...2] Stator resistance (line) / Stator res. (L)
p0352[0...2] Cable resistance / Cable resistance
p0354[0...2] Rotor resistance / Rotor resistance
p0356[0...2] Stator leakage inductance / Stator leak.induct
p0358[0...2] Rotor leakage inductance / Rotor leak.induct.
p0360[0...2] Main inductance / Main inductance
p0362[0...2] Magnetizing curve flux 1 / Magnet.curve flux1
p0363[0...2] Magnetizing curve flux 2 / Magnet.curve flux2
p0364[0...2] Magnetizing curve flux 3 / Magnet.curve flux3
p0365[0...2] Magnetizing curve flux 4 / Magnet.curve flux4
p0366[0...2] Magnetizing curve imag 1 / Magnet.curve imag1
p0367[0...2] Magnetizing curve imag 2 / Magnet.curve imag2
p0368[0...2] Magnetizing curve imag 3 / Magnet.curve imag3
p0369[0...2] Magnetizing curve imag 4 / Magnet.curve imag4
r0370[0...2] Stator resistance [%] / Stator res. [%]
r0372[0...2] Cable resistance [%] / Cable res. [%]
r0373[0...2] Rated stator resistance [%] / Rated stat.res.[%]
r0374[0...2] Rotor resistance [%] / Rotor res. [%]
r0376[0...2] Rated rotor resistance [%] / Rated rot. res.[%]
r0377[0...2] Total leakage reactance [%] / Tot.leak.react.[%]
r0382[0...2] Main reactance [%] / Main reactance [%]
r0384[0...2] Rotor time constant / Rotor time const.
r0386[0...2] Total leakage time constant / Total leak. Tconst
r0394 CO: Stator resistance IGBT [%] / Stat. res.IGBT
r0395 CO: Total stator resistance [%] / Total stat.res
r0396 CO: Act. rotor resistance / Act rotor res.
p0400[0...2] Select encoder type / Select enc. type
r0403.0...4 CO/BO: Encoder status word / Enc. StatWd
p0405[0...2] Enables selection of pulse types / Enables pulse type
p0408[0...2] Encoder pulses per revolution / Enc pulses per rev
p0410[0...2] Reverses internal direction sense / Rev dir sense
r0485 CO: Encoder counter value / Encoder count val.
p0491[0...2] Reaction on speed signal loss / Select enc. type
p0492[0...2] Allowed speed difference / Allowed speed dif
p0494[0...2] Delay speed loss reaction / Dly speed loss rec
p0500[0...2] Technological application / Techn. application
p0601[0...2] Motor temperature sensor / Motor temp. sensor
p0604[0...2] Threshold motor temperature / Thresh. mot. temp.
p0610[0...2] Motor I2t temperature reaction / I2t temp. reaction
p0621[0...2] Motor temp. ident after restart / Mot.temp ident.
p0622[0...2] Magnetizing time for temp id after start up / Magnet. t temp id
r0623[0...2] CO: Display for the identified stator resistance / Act. stator resist
p0625[0...2] Ambient motor temperature / Ambient mot. temp.
p0626[0...2] Overtemperature stator iron / Overtemp.stat.iron
p0627[0...2] Overtemperature stator winding / Overtemp.stat.wind
p0628[0...2] Overtemperature rotor winding / Overtemp.rot. wind
r0630[0...2] CO: Motor model ambient temperature / Mot. model amb. te
r0631[0...2] CO: Stator iron temperature / Stat.iron temp
r0632[0...2] CO: Stator winding temperature / Stat.wind.temp
r0633[0...2] CO: Rotor winding temperature / Rot. wind.temp
p0640[0...2] Motor overload factor [%] / Motor ovl fact [%]
p0700[0...2] Selection of command source / Command source sel
p0700[0...2] Selection of command source / Command source sel
p0701[0...2] Function of digital input 0 / Function of DI0
p0701[0...2] Function of digital input 0 / Function of DI0
p0701[0...2] Function of digital input 0 / Function of DI0
p0701[0...2] Function of digital input 0 / Function of DI0
p0702[0...2] Function of digital input 1 / Function of DI1
p0702[0...2] Function of digital input 1 / Function of DI1
p0702[0...2] Function of digital input 1 / Function of DI1
p0702[0...2] Function of digital input 1 / Function of DI1
p0703[0...2] Function of digital input 2 / Function of DI2
p0703[0...2] Function of digital input 2 / Function of DI2
p0704[0...2] Function of digital input 3 / Function of DI3
p0704[0...2] Function of digital input 3 / Function of DI3
p0705[0...2] Function of digital input 4 / Function of DI4
p0705[0...2] Function of digital input 4 / Function of DI4
p0706[0...2] Function of digital input 5 / Function of DI5
p0706[0...2] Function of digital input 5 / Function of DI5
p0707[0...2] Function of digital input 6 / Function of DI6
p0707[0...2] Function of digital input 6 / Function of DI6
p0708[0...2] Function of digital input 7 / Function of DI7
p0708[0...2] Function of digital input 7 / Function of DI7
p0709[0...2] Function of digital input 8 / Function of DI8
p0709[0...2] Function of digital input 8 / Function of DI8
p0712[0...2] Analog / digital input 0 / Ana/digi input 0
p0712[0...2] Analog / digital input 0 / Ana/digi input 0
p0713[0...2] Analog / digital input 1 / Ana/digi input 1
p0713[0...2] Analog / digital input 1 / Ana/digi input 1
p0719[0...2] Selection of cmd. & freq. setp. / Cmd.&freq.setp.sel
p0719[0...2] Selection of cmd. & freq. setp. / Cmd.&freq.setp.sel
r0720 Number of digital inputs / Number of DI
r0722.0...12 CO/BO: Binary input values / Bin.inp.val
r0722.0...12 CO/BO: Binary input values / Bin.inp.val
p0724 Debounce time for digital inputs / Debounce time: DI
p0725 PNP / NPN digital inputs / PNP/NPN DI
p0727[0...2] Selection of 2/3-wire method / 2/3wire selection
r0730 Number of digital outputs / Number of DO
p0731[0...2] BI: Function of digital output 0 / Fct. of DO0
p0731[0...2] BI: Function of digital output 0 / Fct. of DO0
p0732[0...2] BI: Function of digital output 1 / Fct. of DO1
p0733[0...2] BI: Function of digital output 2 / Fct. of DO2
r0747.0...2 CO/BO: State of digital outputs / State DOs
p0748 Invert digital outputs / Invert DOs
r0750 Number of AIs / Number of AIs
r0751.0...9 CO/BO: Status word of AI / AI status Wd
r0752[0...1] Act. input of AI [V] or [mA] / Act.AI inp.[V/mA]
p0753[0...1] Smooth time AI / Smooth time AI
r0754[0...1] Act. AI value after scaling [%] / AI after scal.[%]
r0755[0...1] CO: Act. AI after scal. [4000h] / CO:AI scal[4000h]
p0756[0...1] Type of AI / Type of AI
p0757[0...1] Value x1 of AI scaling / Value x1:AI scal.
p0758[0...1] Value y1 of AI scaling / Value y1:AI scal.
p0759[0...1] Value x2 of AI scaling / Value x2:AI scal.
p0760[0...1] Value y2 of AI scaling / Value y2:AI scal.
p0761[0...1] Width of AI deadband / AI deadband width
p0762[0...1] Delay for loss of signal action / Delay on sig. loss
r0770 Number of AO / Number of AO
p0771[0...1] CI: AO / AO
p0773[0...1] Smooth time AO / Smooth time AO
r0774[0...1] Act. AO value [V] or [mA] / Act.AO val.[V/mA]
p0775[0...1] Permit absolute value / Enable ab. value
p0776[0...1] Type of AO / Type of AO
p0777[0...1] Value x1 of AO scaling / Value x1:AO scal.
p0778[0...1] Value y1 of AO scaling / Value y1:AO scal.
p0779[0...1] Value x2 of AO scaling / Value x2:AO scal.
p0780[0...1] Value y2 of AO scaling / Value y2:AO scal.
p0781[0...1] Width of AO deadband / AO deadband width
r0785.0...1 CO/BO: Status word of AO / AO stat Wd
p0800[0...2] BI: Download parameter set 0 / Dwnl.par.set 0
p0801[0...2] BI: Download parameter set 1 / Dwnl.par.set 1
p0802 Transfer data from EEPROM / Transf.Drive>Ext
p0802 Transfer data from EEPROM / Transf.Drive>Ext
p0803 Transfer data to EEPROM / Transf.Ext>Drive
p0803 Transfer data to EEPROM / Transf.Ext>Drive
p0804 Select Clone file / Select Clone file
p0806 BI: Inhibit panel access / Inhibit panel acce
r0807.0 BO: Displays client access / Displays client ac
p0809[0...2] Copy Command Dataset (CDS) / Copy CDS
p0810 BI: CDS bit 0 (Hand/Auto) / CDS bit 0
p0811 BI: CDS bit 1 / CDS bit 1
p0819[0...2] Copy Drive Dataset (DDS) / Copy DDS
p0820 BI: DDS bit 0 / DDS bit 0
p0821 BI: DDS bit 1 / DDS bit 1
p0840[0...2] BI: ON/OFF1 / ON/OFF1
p0840[0...2] BI: ON/OFF1 / ON/OFF1
p0840[0...2] BI: ON/OFF1 / ON/OFF1
p0840[0...2] BI: ON/OFF1 / ON/OFF1
p0840[0...2] BI: ON/OFF1 / ON/OFF1
p0842[0...2] BI: ON reverse/OFF1 / ON reverse/OFF1
p0844[0...2] BI: 1. OFF2 / 1. OFF2
p0844[0...2] BI: 1. OFF2 / 1. OFF2
p0844[0...2] BI: 1. OFF2 / 1. OFF2
p0845[0...2] BI: 2. OFF2 / 2. OFF2
p0848[0...2] BI: 1. OFF3 / 1. OFF3
p0848[0...2] BI: 1. OFF3 / 1. OFF3
p0848[0...2] BI: 1. OFF3 / 1. OFF3
p0849[0...2] BI: 2. OFF3 / 2. OFF3
p0852[0...2] BI: Pulse enable / Pulse enable
p0852[0...2] BI: Pulse enable / Pulse enable
p0852[0...2] BI: Pulse enable / Pulse enable
p0918 PROFIBUS address / PROFIBUS address
p0922 Selection of PROFIdrive Standard Telegram / Standard Telegram
p0927 Parameter changeable via / Change par. via
p0927 Parameter changeable via / Change par. via
r0944 Total number of messages / Total nb Mes
r0947[0...63] CO: Last fault code / Last fault code
r0947[0...63] CO: Last fault code / Last fault code
r0948[0...63] Fault time / Fault time
r0948[0...63] Fault time / Fault time
r0949[0...63] CO: Fault value / Fault value
p0952 Total number of faults / Total faults
r0964[0...6] Firmware version data / FW version data
r0965 PROFIdrive Profile / PROFIdrive Profile
r0967 Control word 1 / Control word 1
r0968 Status word 1 / Status word 1
p0969 Resetable system run time counter / Rst counter
p0970 Factory reset / Factory reset
p0970 Factory reset / Factory reset
p0971 Transfer data from RAM to EEPROM / Transf.RAM>EEPROM
r0975[0...10] DO identification / DO ident.
r0980[0...99] List of avaiable parameter numbers / Paramter list
r0981[0...99] List of avaiable parameter numbers / Paramter list
r0982[0...99] List of avaiable parameter numbers / Paramter list
r0983[0...99] List of avaiable parameter numbers / Paramter list
r0984[0...99] List of avaiable parameter numbers / Paramter list
r0985[0...99] List of avaiable parameter numbers / Paramter list
r0986[0...99] List of avaiable parameter numbers / Paramter list
r0987[0...99] List of avaiable parameter numbers / Paramter list
r0988[0...99] List of avaiable parameter numbers / Paramter list
r0989[0...99] List of avaiable parameter numbers / Paramter list
p1000[0...2] Selection of frequency setpoint / Freq setp. select.
p1000[0...2] Selection of frequency setpoint / Freq setp. select.
p1001[0...2] Fixed frequency 1 / Fixed frequency 1
p1002[0...2] Fixed frequency 2 / Fixed frequency 2
p1003[0...2] Fixed frequency 3 / Fixed frequency 3
p1004[0...2] Fixed frequency 4 / Fixed frequency 4
p1005[0...2] Fixed frequency 5 / Fixed frequency 5
p1006[0...2] Fixed frequency 6 / Fixed frequency 6
p1007[0...2] Fixed frequency 7 / Fixed frequency 7
p1008[0...2] Fixed frequency 8 / Fixed frequency 8
p1009[0...2] Fixed frequency 9 / Fixed frequency 9
p1010[0...2] Fixed frequency 10 / Fixed frequency 10
p1011[0...2] Fixed frequency 11 / Fixed frequency 11
p1012[0...2] Fixed frequency 12 / Fixed frequency 12
p1013[0...2] Fixed frequency 13 / Fixed frequency 13
p1014[0...2] Fixed frequency 14 / Fixed frequency 14
p1015[0...2] Fixed frequency 15 / Fixed frequency 15
p1016[0...2] Fixed frequency mode / FF mode
p1020[0...2] BI: Fixed freq. selection Bit 0 / FF sel. Bit 0
p1021[0...2] BI: Fixed freq. selection Bit 1 / FF sel. Bit 1
p1022[0...2] BI: Fixed freq. selection Bit 2 / FF sel. Bit 2
p1023[0...2] BI: Fixed freq. selection Bit 3 / FF sel. Bit 3
p1023[0...2] BI: Fixed freq. selection Bit 3 / FF sel. Bit 3
r1024 CO: Act. fixed frequency / Act. FF
r1025.0 BO: Fixed frequency status / FF Status
p1031[0...2] MOP mode / MOP mode
p1032 Inhibit reverse direction of MOP / Inhib. MOP reverse
p1035[0...2] BI: Enable MOP (UP-command) / Enable MOP(UP)
p1035[0...2] BI: Enable MOP (UP-command) / Enable MOP(UP)
p1035[0...2] BI: Enable MOP (UP-command) / Enable MOP(UP)
p1036[0...2] BI: Enable MOP (DOWN-command) / Enable MOP(DWN)
p1036[0...2] BI: Enable MOP (DOWN-command) / Enable MOP(DWN)
p1036[0...2] BI: Enable MOP (DOWN-command) / Enable MOP(DWN)
p1040[0...2] Setpoint of the MOP / MOP setpoint
p1041[0...2] BI: MOP select setpoint automatically/manually / Setp. auto/manu
p1042[0...2] CI: MOP auto setpoint / MOP auto setpoint
p1043[0...2] BI: MOP accept rampgenerator setpoint / MOP acc RFG setpo
p1044[0...2] CI: MOP rampgenerator setpoint / MOP RFG setpoint
r1045 CO: MOP input frequency of the RFG / MOP RFG input
p1047[0...2] MOP ramp-up time of the RFG / MOP rampup time
p1048[0...2] MOP ramp-down time of the RFG / MOP rampdown time
r1050 CO: Act. Output freq. of the MOP / MOP outp.freq.
p1055[0...2] BI: Enable JOG right / Enable JOG >
p1055[0...2] BI: Enable JOG right / Enable JOG >
p1055[0...2] BI: Enable JOG right / Enable JOG >
p1056[0...2] BI: Enable JOG left / Enable JOG <
p1056[0...2] BI: Enable JOG left / Enable JOG <
p1056[0...2] BI: Enable JOG left / Enable JOG <
p1057 JOG Enable / JOG Enable
p1058[0...2] JOG frequency / JOG frequency
p1059[0...2] JOG frequency left / JOG frequency <
p1060[0...2] JOG ramp-up time / JOG rampup time
p1061[0...2] JOG ramp-down time / JOG rampdown time
p1070[0...2] CI: Main setpoint / Main setpoint
p1070[0...2] CI: Main setpoint / Main setpoint
p1071[0...2] CI: Main setpoint scaling / Main setp scal
p1074[0...2] BI: Disable additional setpoint / Disab.add.setp
p1075[0...2] CI: Additional setpoint / Add. setpoint
p1076[0...2] CI: Additional setpoint scaling / Add. setp.scal
r1078 CO: Total frequency setpoint / Tot. freq.setp
r1079 CO: Selected frequency setpoint / Sel. freq.setp
p1080[0...2] Min. frequency / Min. frequency
p1082[0...2] Max. frequency / Max. frequency
p1082[0...2] Max. frequency / Max. frequency
r1084 Resultant max. frequency / Resultant max freq
p1091[0...2] Skip frequency / Skip frequency
p1092[0...2] Skip frequency 2 / Skip frequency 2
p1093[0...2] Skip frequency 3 / Skip frequency 3
p1094[0...2] Skip frequency 4 / Skip frequency 4
p1101[0...2] Skip frequency bandwidth / Skipfreq bandwidth
p1110[0...2] BI: Inhibit neg. freq. setpoint / Inh. neg. setp
p1113[0...2] BI: Reverse / Reverse
p1113[0...2] BI: Reverse / Reverse
p1113[0...2] BI: Reverse / Reverse
r1114 CO: Freq. setp. after dir. ctrl. / Setp<dir.ctrl.
r1119 CO: Freq. setpoint before RFG / Setp before RFG
p1120[0...2] Ramp-up time / Rampup time
p1121[0...2] Ramp-down time / Rampdown time
p1124[0...2] BI: Enable JOG ramp times / Enable JOG ramp
p1130[0...2] Ramp-up initial rounding time / Rampup ini. Trnd
p1131[0...2] Ramp-up final rounding time / Rampup final Trnd
p1132[0...2] Ramp-down initial rounding time / Rampdwn ini. Trnd
p1133[0...2] Ramp-down final rounding time / Rampdwn fin. Trnd
p1134[0...2] Rounding type / Rounding type
p1135[0...2] OFF3 ramp-down time / OFF3 rampdwn time
p1140[0...2] BI: RFG enable / RFG enable
p1140[0...2] BI: RFG enable / RFG enable
p1140[0...2] BI: RFG enable / RFG enable
p1141[0...2] BI: RFG start / RFG start
p1141[0...2] BI: RFG start / RFG start
p1141[0...2] BI: RFG start / RFG start
p1142[0...2] BI: RFG enable setpoint / RFG enable setp
p1142[0...2] BI: RFG enable setpoint / RFG enable setp
p1142[0...2] BI: RFG enable setpoint / RFG enable setp
r1170 CO: Frequency setpoint after RFG / Setp. after RFG
p1200 Flying start / Flying start
p1202[0...2] Motor-current: Flying start / Mot. cur: Flystart
p1203[0...2] Search rate: Flying start / SrchRate: Flystart
r1204 Status word: Flying start V/f / Stat: Flystart V/f
r1205 Status word: Flying start SLVC / Stat Flystart SLVC
p1210 Automatic restart / Automatic restart
p1211 Number of restart attempts / Restart attempts
p1215 Holding brake enable / MHB enable
p1215 Holding brake enable / MHB enable
p1216 Holding brake release delay / MHB release delay
p1217 Holding time after ramp down / Thold. < rampdwn
p1218[0...2] BI: MHB override / MHB override
p1227[0...2] Zero speed detection monitoring time / Zero speed time
p1230[0...2] BI: Enable DC braking / Enable DC brk.
p1232[0...2] DC braking current / DC braking current
p1233[0...2] Duration of DC braking / DC brak. duration
p1234[0...2] DC braking start frequency / DC brk. start freq
p1236[0...2] Compound braking current / Compound brk. cur.
p1237 Dynamic braking / Dynamic braking
p1240[0...2] Configuration of Vdc controller / Vdc controller
r1242 CO: Switch-on level of Vdc-max / Vdcmax ON lev
p1243[0...2] Dynamic factor of Vdc-max / Vdcmax dyn. fact.
p1245[0...2] Switch on level kin. buffering / KIB ON level
r1246[0...2] CO: Switch-on level kin buffering / KIB ON level
p1247[0...2] Dyn. factor of kinetic buffering / Dyn. factor of KIB
p1250[0...2] Gain of Vdc-controller / Gain of Vdc ctrl.
p1251[0...2] Integration time Vdc-controller / Int. time Vdc ctrl
p1252[0...2] Differential time Vdc-controller / Diff.time Vdc ctrl
p1253[0...2] Vdc-controller output limitation / Vdc ctrl outp. lim
p1254 Auto detect Vdc switch-on levels / Autodet Vdc ON lev
p1256[0...2] Reaction of kinetic buffering / Reaction of KIB
p1257[0...2] Freq limit for kinetic buffering / Freq limit for KIB
p1300[0...2] Control mode / Control mode
p1300[0...2] Control mode / Control mode
p1310[0...2] Continuous boost / Continuous boost
p1311[0...2] Acceleration boost / Acceleration boost
p1312[0...2] Starting boost / Starting boost
r1315 CO: Total boost voltage / Total boost V
p1316[0...2] Boost end frequency / Boost end freq.
p1320[0...2] Programmable V/f freq. coord. 1 / V/f freq. coord. 1
p1321[0...2] Programmable V/f volt. coord. 1 / V/f volt. coord. 1
p1322[0...2] Programmable V/f freq. coord. 2 / V/f freq. coord. 2
p1323[0...2] Programmable V/f volt. coord. 2 / V/f volt. coord. 2
p1324[0...2] Programmable V/f freq. coord. 3 / V/f freq. coord. 3
p1325[0...2] Programmable V/f volt. coord. 3 / V/f volt. coord. 3
p1330[0...2] CI: Voltage setpoint / Voltage setp.
p1333[0...2] Start frequency for FCC / Start freq for FCC
p1334[0...2] Slip compensation activation range / Slip c. act. range
p1335[0...2] Slip compensation / Slip compensation
p1336[0...2] Slip limit / Slip limit
r1337 CO: V/f slip frequency / V/f slip freq.
p1338[0...2] Resonance damping gain V/f / Res.damp. gain V/f
p1340[0...2] Imax controller prop. gain / Imax ctrl prp gain
p1341[0...2] Imax controller integral time / Imax ctrl int time
r1343 CO: Imax controller freq. output / Imax ctrl Foutp
r1344 CO: Imax controller volt. output / Imax ctrl Voutp
p1345[0...2] Imax voltage ctrl. prop. gain / Imax volt prp gain
p1346[0...2] Imax voltage ctrl. integral time / Imax volt int time
p1350[0...2] Voltage soft start / Voltage soft start
p1400[0...2] Configuration of speed control / Config. of nctrl.
r1407.0...15 CO/BO: Status 2 of motor control / Stat 2 ctrl
r1438 CO: Freq. setpoint to controller / Freq. setp ctl
p1442[0...2] Filter time for act. speed / Filter time n_act.
r1445 CO: Act. filtered frequency / Act. filt freq
p1452[0...2] Filter time for act.speed (SLVC) / Act.spd.filt. SLVC
p1460[0...2] Gain speed controller / Gain of nctrl.
p1462[0...2] Integral time speed controller / Tn of nctrl.
p1470[0...2] Gain speed controller (SLVC) / Gain nctrl (SLVC)
p1472[0...2] Integral time n-ctrl. (SLVC) / Tn of nctrl. SLVC
p1477[0...2] BI: Set integrator of n-ctrl. / Set integrator
p1478[0...2] CI: Set integrator value n-ctrl. / Set int. value
r1482 CO: Integral output of n-ctrl. / Int.outp nctrl
p1488[0...2] Droop input source / Droop input source
p1489[0...2] Droop scaling / Droop scaling
r1490 CO: Droop frequency / Droop freq.
p1492[0...2] BI: Enable droop / Enable droop
p1496[0...2] Scaling accel. precontrol / Scal acc. prectrl.
p1496[0...2] Scaling accel. precontrol / Scal acc. prectrl.
p1496[0...2] Scaling accel. precontrol / Scal acc. prectrl.
p1499[0...2] Scaling accel. torque control / Scal acc. trq ctrl
p1500[0...2] Selection of torque setpoint / Torque setp. sel.
p1500[0...2] Selection of torque setpoint / Torque setp. sel.
p1501[0...2] BI: Change to torque control / Change > torq ctrl
p1501[0...2] BI: Change to torque control / Change > torq ctrl
p1503[0...2] CI: Torque setpoint / Torque setp.
r1508 CO: Torque setpoint / Torque setp.
p1511[0...2] CI: Additional torque setpoint / Add. trq. setp
r1515 CO: Additional torque setpoint / Add. trq. setp
r1518 CO: Acceleration torque / Accel. torque
p1520[0...2] CO: Upper torque limit / Upper trq. lim
p1521[0...2] CO: Lower torque limit / Lower trq. lim
p1522[0...2] CI: Upper torque limit / Upper trq. lim
p1523[0...2] CI: Lower torque limit / Lower trq. lim
p1525[0...2] Scaling lower torque limit / Scal. low trq. lim
r1526 CO: Upper torque limitation / Upper trq. lim
r1527 CO: Lower torque limitation / Lower trq. lim
p1530[0...2] Motoring power limitation / Motoring power lim
p1531[0...2] Regenerative power limitation / Regener. power lim
r1536 CO: Max. trq. motoring current / Max trq mot cur
r1537 CO: Max trq regenerative current / Max trq reg cur
r1538 CO: Upper torque limit (total) / Total up TrqLim
r1539 CO: Lower torque limit (total) / Total lw TrqLim
p1570[0...2] CO: Fixed value flux setpoint / Fval flux setp
p1574[0...2] Dynamic voltage headroom / Dyn. volt headroom
p1580[0...2] Efficiency optimization / Efficiency optimiz
p1582[0...2] Smooth time for flux setpoint / Flux setp. Tsmooth
r1583 CO: Flux setpoint (smoothed) / Smoothed setp.
p1596[0...2] Int. time field weak. controller / Int.time weak.ctrl
r1597 CO: Outp. field weak. controller / Outp.weak. ctrl
r1598 CO: Flux setpoint (total) / Total flux setp
p1610[0...2] Continuous torque boost (SLVC) / Cont. torque boost
p1611[0...2] Acc. torque boost (SLVC) / Acc trq boost SLVC
p1654[0...2] Smooth time for Isq setpoint / Isq setp. Tsmooth
p1715[0...2] Gain current controller / Gain current ctrl.
p1717[0...2] Integral time current controller / Int.time cur. ctrl
r1718 CO: Output of Isq controller / Outp. Isq ctrl
r1719 CO: Integral output of Isq ctrl. / Int. outp. Isq
r1723 CO: Output of Isd controller / Outp. Isd ctrl
r1724 CO: Integral output of Isd ctrl. / Int. outp. Isd
r1725 CO: Integral limit of Isd ctrl. / Int. limit Isd
r1728 CO: Decoupling voltage / Decoupl. volt
p1740 Gain for oscillation damping / Oscill. damp. gain
p1745[0...2] Flux variance limit in stall / Flux var.lim.stall
r1746 CO: Actual flux variance / Act. flux variance
p1750[0...2] Control word of motor model / Motor model CtrlWd
r1751.0...15 CO/BO: Status word of motor model / Motor model StatWd
p1752[0...2] Start-freq. speed adaption (VC with encoder) / Startfreq. (VC)
p1755[0...2] Start-freq. motor model (SLVC) / Startfreq. (SLVC)
p1756[0...2] Hyst.-freq. motor model (SLVC) / Hyst. freq. (SLVC)
p1758[0...2] T(wait) transit to open-loop / T(wait) trans.>OL
p1759[0...2] T(wait) transit to closed-loop / T(wait) trans.>CL
p1764[0...2] Kp of n-adaption (SLVC) / Kp nadapt. (SLVC)
p1767[0...2] Tn of n-adaption (SLVC) / Tn nadapt. (SLVC)
r1770 CO: Prop. output of n-adaption / Prop outp nad
r1771 CO: Int. output of n-adaption / Int. outp nad
r1778 CO: Flux angle difference / Flux angle diff
p1780[0...2] Control word of Rs/Rr-adaption / CtrlWd Rs/Rr adapt
p1781[0...2] Tn of Rs-adaption / Tn of Rsadaption
r1782 CO: Output of Rs-adaptation / Output Rsadaption
p1786[0...2] Tn of Xm-adaption / Tn of Xmadaption
r1787 CO: Output of Xm-adaption / Outp. Xmadaption
p1800[0...2] Pulse frequency / Pulse frequency
r1801[0...1] CO: Pulse frequency / Pulse frequency
p1802 Modulator mode / Modulator mode
p1803[0...2] Max. modulation / Max. modulation
p1810 Control word Vdc control / Control word vdc c
p1820[0...2] Reverse output phase sequence / Rev.outp.phase seq
p1825 On-state voltage of IGBT / Onstate voltage
p1828 Gating unit dead time / Gating dead time
p1860 Filter control word / Filter control wor
r1861 Filter correction voltage (alpha-component) / Filter correction
r1862 Filter correction voltage (beta-component) / Filter correction
r1863 Filter correction current (alpha-component) / Filter correction
r1864 Filter correction current (beta-component) / Filter correction
p1900 Select motor data identification / Sel.mot.data ident
p1900 Select motor data identification / Sel.mot.data ident
p1909[0...2] Ctrl. word of motor data ident. / Ctrl.mot.data id.
p1910 Select motor data identification extended / Sel.mot.data ident
p1910 Select motor data identification extended / Sel.mot.data ident
p1911 No. of phase to be identified / No.of phase for id
r1912[0...2] Identified stator resistance / Identif. stat. res
r1913[0...2] Identified rotor time constant / Identif.rot.Tconst
r1914[0...2] Ident. total leakage inductance / Tot.leak.induct.
r1915[0...2] Ident. nom. stator inductance / Nom.stat.induct.
r1916[0...2] Identified stator inductance 1 / Stator induct. 1
r1917[0...2] Identified stator inductance 2 / Stator induct. 2
r1918[0...2] Identified stator inductance 3 / Stator induct. 3
r1919[0...2] Identified stator inductance 4 / Stator induct. 4
r1920[0...2] Identified dyn. leak. inductance / Dyn. leak. induct.
r1925[0...2] Identified on-state voltage / Id. onstate V.
r1926 Ident. gating unit dead time / Id.gating deadtime
p1930 Voltage setpoint for calibration / Volt setp. calibr.
p1931 Phase / Phase
p1960 Speed control optimisation / Speed control opt.
p1960 Speed control optimisation / Speed control opt.
p2000[0...2] Reference frequency / Reference freq.
p2001[0...2] Reference voltage / Reference voltage
p2002[0...2] Reference current / Reference current
p2003[0...2] Reference torque / Reference torque
p2004[0...2] Reference power / Reference power
p2004[0...2] Reference power / Reference power
p2010[0...1] USS baudrate / USS baudrate
p2011[0...1] USS address / USS address
p2012[0...1] USS PZD length / USS PZD length
p2013[0...1] USS PKW length / USS PKW length
p2014[0...1] USS telegram off time / USS telegram T_off
r2015[0...7] CO: PZD from USS on RS232 / PZD<USS
p2016[0...7] CI: PZD to USS on RS232 / PZD>USS
r2018[0...7] CO: PZD from USS on RS485 / PZD<COM(USS)
p2019[0...7] CI: PZD to USS on RS485 (USS) / PZD>COM (USS)
r2024[0...1] USS error-free telegrams / USS errorfree tel
r2025[0...1] USS rejected telegrams / USS rejected tel.
r2026[0...1] USS character frame error / USS char.frame err
r2027[0...1] USS overrun error / USS overrun error
r2028[0...1] USS parity error / USS parity error
r2029[0...1] USS start not identified / USS start unident.
r2030[0...1] USS BCC error / USS BCC error
r2031[0...1] USS length error / USS length error
r2032.0...15 BO: CtrlWrd1 from USS on RS232 / CtrlWd1 < USS
r2033.0...15 BO: CtrlWrd2 from USS on RS232 / CtrlWd2 < USS
r2033.0...15 BO: CtrlWrd2 from USS on RS232 / CtrlWd2 < USS
r2036.0...15 BO: CtrlWrd1 from USS on RS485 (USS) / CtrlWd 1 < COM
r2037.0...15 BO: CtrlWrd2 from USS on RS485 (USS) / CtrlWd2 < COM
r2037.0...15 BO: CtrlWrd2 from USS on RS485 (USS) / CtrlWd2 < COM
p2038 Selection of actual profile / Actual profile
p2038 Selection of actual profile / Actual profile
p2040 Fieldbus telegram off time / FB tel. off time
p2041[0...4] FB parameter / FB parameter
p2042 Selection of ident number / Ident nb
r2050[0...7] CO: PZD from Fieldbus / PZD from FB
p2051[0...7] CI: PZD to Fieldbus / PZD to FB
r2053[0...7] FB identification / FB identification
r2054[0...15] FB diagnosis / FB diagnosis
r2058[0...15] FB rev config / FB rev config
r2059[0...4] CO: Displays SOL link stats for Sol Master. / Disp SOL stats
r2090.0...15 BO: Control word 1 from Fieldbus / CtrlWd1 < FB
r2091.0...15 BO: Control word 2 from Fieldbus / CtrlWd2 < FB
r2091.0...15 BO: Control word 2 from Fieldbus / CtrlWd2 < FB
p2100[0...2] Alarm number selection / Alarm No selection
p2101[0...2] Stop reaction value / Stop reaction val.
p2103[0...2] BI: 1. Faults acknowledgement / 1. Faults ackn
p2104[0...2] BI: 2. Faults acknowledgement / 2. Faults ackn
p2104[0...2] BI: 2. Faults acknowledgement / 2. Faults ackn
p2104[0...2] BI: 2. Faults acknowledgement / 2. Faults ackn
p2106[0...2] BI: External fault / External fault
r2110[0...3] CO: Warning number / Warning number
p2111 Total number of warnings / Total no. warnings
r2114[0...1] Run time counter / Run time counter
p2115[0...2] Real time clock / Real time clk
p2120 Indication counter / Indication counter
r2131 CO: Last fault number code / Last fault code
r2132 CO: First warning number code / First warning code
p2150[0...2] Hysteresis frequency f_hys / Hyst. freq. f_hys
p2151[0...2] CI: Speed setpoint for messages / nSet for msg
p2152[0...2] Delay time of f>fmax / Delay f>fmax
p2153[0...2] Time-constant speed filter / Tconst. speed filt
p2155[0...2] Threshold frequency f_1 / Threshold freq f_1
p2156[0...2] Delay time of threshold freq f_1 / Delay time of f_1
p2157[0...2] Threshold frequency f_2 / Threshold freq f_2
p2158[0...2] Delay time of threshold freq f_2 / Delay time of f_2
p2159[0...2] Threshold frequency f_3 / Threshold freq f_3
p2160[0...2] Delay time of threshold freq f_3 / Delay time of f_3
p2161[0...2] Min. threshold for freq. setp. / Setp.min.threshold
p2162[0...2] Hysteresis freq. for overspeed / Overspd. hyst.freq
p2163[0...2] Entry freq. for perm. deviation / Entry freq. deviat
p2164[0...2] Hysteresis frequency deviation / Hyster freq deviat
p2165[0...2] Delay time permitted deviation / Delay_T perm. dev.
p2166[0...2] Delay time ramp up completed / Delay_T rampUpCmpl
p2167[0...2] Switch-off frequency f_off / SwOff freq. f_off
p2168[0...2] Delay time T_off / Delay time T_off
r2169 CO: Act. filtered frequency / Act. filt. freq
p2170[0...2] Threshold current I_thresh / Threshold current
p2171[0...2] Delay time current / Delay time current
p2172[0...2] Threshold DC-link voltage / Vdc threshold
p2173[0...2] Delay time DC-link voltage / Vdc delay time
p2174[0...2] Torque threshold M_thresh / Torque threshold
p2176[0...2] Delay time for torque threshold / Delay time torque
p2177[0...2] Delay time for motor is blocked / Delay_T MotBlocked
p2178[0...2] Delay time for motor pulled out / Delay_T MotPullOut
p2179 Current limit for no load ident. / Cur.lim:noload ID
p2180 Delay time for load missing / Load missing delay
p2181[0...2] Belt failure detection mode / Belt fail detect
p2182[0...2] Belt threshold frequency 1 / Belt threshold f_1
p2183[0...2] Belt threshold frequency 2 / Belt threshold f_2
p2184[0...2] Belt threshold frequency 3 / Belt threshold f_3
p2185[0...2] Upper torque threshold 1 / Upper trq. thresh1
p2186[0...2] Lower torque threshold 1 / Lower trq. thresh1
p2187[0...2] Upper torque threshold 2 / Upper trq. thresh2
p2188[0...2] Lower torque threshold 2 / Lower trq. thresh2
p2189[0...2] Upper torque threshold 3 / Upper trq. thresh3
p2190[0...2] Lower torque threshold 3 / Lower trq. thresh3
p2192[0...2] Time delay for belt failure / Belt fail delay_T
r2197.0...12 CO/BO: Monitoring word 1 / Monitor Wd1
r2197.0...12 CO/BO: Monitoring word 1 / Monitor Wd1
r2198.0...12 CO/BO: Monitoring word 2 / Monitor Wd2
p2200[0...2] BI: Enable PID controller / Enab. PID ctrl
p2201[0...2] Fixed PID setpoint 1 / Fixed PID setp. 1
p2202[0...2] Fixed PID setpoint 2 / Fixed PID setp. 2
p2203[0...2] Fixed PID setpoint 3 / Fixed PID setp. 3
p2204[0...2] Fixed PID setpoint 4 / Fixed PID setp. 4
p2205[0...2] Fixed PID setpoint 5 / Fixed PID setp. 5
p2206[0...2] Fixed PID setpoint 6 / Fixed PID setp. 6
p2207[0...2] Fixed PID setpoint 7 / Fixed PID setp. 7
p2208[0...2] Fixed PID setpoint 8 / Fixed PID setp. 8
p2209[0...2] Fixed PID setpoint 9 / Fixed PID setp. 9
p2210[0...2] Fixed PID setpoint 10 / Fixed PID setp. 10
p2211[0...2] Fixed PID setpoint 11 / Fixed PID setp. 11
p2212[0...2] Fixed PID setpoint 12 / Fixed PID setp. 12
p2213[0...2] Fixed PID setpoint 13 / Fixed PID setp. 13
p2214[0...2] Fixed PID setpoint 14 / Fixed PID setp. 14
p2215[0...2] Fixed PID setpoint 15 / Fixed PID setp. 15
p2216[0...2] Fixed PID setpoint mode / Fix.PID Mode
p2220[0...2] BI: Fixed PID setp. select Bit 0 / PID setp>Bit 0
p2221[0...2] BI: Fixed PID setp. select Bit 1 / PID setp>Bit 1
p2222[0...2] BI: Fixed PID setp. select Bit 2 / PID setp>Bit 2
p2223[0...2] BI: Fixed PID setp. select Bit 3 / PID setp>Bit 3
p2223[0...2] BI: Fixed PID setp. select Bit 3 / PID setp>Bit 3
r2224 CO: Act. fixed PID setpoint / Fixed.PID setp
r2225.0 BO: PID Fixed frequency status / PID FF Status
p2231[0...2] PID-MOP mode / PIDMOP mode.
p2232 Inhibit rev. direct. of PID-MOP / Inhib. PIDMOD rev
p2235[0...2] BI: Enable PID-MOP (UP-cmd) / PIDMOP (UP)
p2236[0...2] BI: Enable PID-MOP (DOWN-cmd) / PIDMOP (DWN)
p2240[0...2] Setpoint of PID-MOP / Setp. of PIDMOP
p2241[0...2] BI: PID-MOP select setpoint auto/manu / Setp. auto/manu
p2242[0...2] CI: PID-MOP auto setpoint / PMOP auto setpoint
p2243[0...2] BI: PID-MOP accept rampgenerator setpoint / PMOP acc RFG setpo
p2244[0...2] CI: PID-MOP rampgenerator setpoint / PMOP RFG setpoint
r2245 CO: PID-MOP input frequency of the RFG / PMOP RFG input
p2247[0...2] PID-MOP ramp-up time of the RFG / PMOP rampup time
p2248[0...2] PID-MOP ramp-down time of the RFG / PMOP rampdown time
r2250 CO: Output setpoint of PID-MOP / PMOP outp. setp
p2251 PID mode / PID mode
p2253[0...2] CI: PID setpoint / PID setpoint
p2254[0...2] CI: PID trim source / PID trim source
p2255 PID setpoint gain factor / PID setp.gain fact
p2256 PID trim gain factor / PID trim gain fact
p2257 Ramp-up time for PID setpoint / PID setp. rampup
p2258 Ramp-down time for PID setpoint / PID setp. rampdwn
r2260 CO: PID setpoint after PID-RFG / PID setp <RFG
p2261 PID setpoint filter timeconstant / PID setp.filt.Tcon
r2262 CO: Filtered PID setp. after RFG / Filt. PID setp
p2263 PID controller type / PID ctrl. type
p2264[0...2] CI: PID feedback / PID feedback
p2265 PID feedback filter timeconstant / Fdbck.filt. Tconst
r2266 CO: PID filtered feedback / PID filt.fdbck
p2267 Max. value for PID feedback / PID fdbck max. val
p2268 Min. value for PID feedback / PID fdbck min. val
p2269 Gain applied to PID feedback / PID feedback gain
p2270 PID feedback function selector / PID fdbck fnct sel
p2271 PID transducer type / PID trans. type
r2272 CO: PID scaled feedback / PID scal fdbck
r2273 CO: PID error / PID error
p2274 PID derivative time / PID deriv. time
p2280 PID proportional gain / PID prop. gain
p2285 PID integral time / PID integral time
p2291 PID output upper limit / PID outp.upper lim
p2292 PID output lower limit / PID outp.lower lim
p2293 Ramp-up /-down time of PID limit / PID lim. ramp time
r2294 CO: Act. PID output / Act.PID output
p2295 Gain applied to PID output / PID output scale
p2350 PID autotune enable / PID autotune
p2354 PID tuning timeout length / PID tuning t/o.
p2355 PID tuning offset / PID tuning offset
p2470[0...2] Encoder speed scaling factor / Encod speed scal
r2477 CO: Act. scaled encoder speed / Act scal enc speed
r2478 CO: Act. scaled encoder frequency / Act scal enc freq
p2480[0...2] BI: Enable positioning ramp down / Enable positioning
p2481[0...2] Gearbox ratio input / Gearbox ratio in
p2482[0...2] Gearbox ratio output / Gearbox ratio out
p2484[0...2] No. of shaft turns = 1 Unit / Position ref. unit
p2487[0...2] Positional error trim value / Positional trim / Positional error
p2488[0...2] Distance / No. of revolutions / Distance / No. rev
r2489[0...2] CO: Tracking parameter / Track / Tracking parameter
p2800 Enable FFBs / Enable FFBs
p2801[0...16] Activate FFBs / Activate FFBs
p2802[0...13] Activate FFBs / Activate FFBs
p2803[0...2] Enable FastFFBs / Enable FastFFBs
p2810[0...1] BI: AND 1 / AND 1
r2811.0 BO: AND 1 / AND 1
p2812[0...1] BI: AND 2 / AND 2
r2813.0 BO: AND 2 / AND 2
p2814[0...1] BI: AND 3 / AND 3
r2815.0 BO: AND 3 / AND 3
p2816[0...1] BI: OR 1 / OR 1
r2817.0 BO: OR 1 / OR 1
p2818[0...1] BI: OR 2 / OR 2
r2819.0 BO: OR 2 / OR 2
p2820[0...1] BI: OR 3 / OR 3
r2821.0 BO: OR 3 / OR 3
p2822[0...1] BI: XOR 1 / XOR 1
r2823.0 BO: XOR 1 / XOR 1
p2824[0...1] BI: XOR 2 / XOR 2
r2825.0 BO: XOR 2 / XOR 2
p2826[0...1] BI: XOR 3 / XOR 3
r2827.0 BO: XOR 3 / XOR 3
p2828 BI: NOT 1 / NOT 1
r2829.0 BO: NOT 1 / NOT 1
p2830 BI: NOT 2 / NOT 2
r2831.0 BO: NOT 2 / NOT 2
p2832 BI: NOT 3 / NOT 3
r2833.0 BO: NOT 3 / NOT 3
p2834[0...3] BI: D-FF 1 / DFF 1
r2835.0 BO: Q D-FF 1 / Q DFF 1
r2836.0 BO: NOT-Q D-FF 1 / NOTQ DFF 1
p2837[0...3] BI: D-FF 2 / DFF 2
r2838.0 BO: Q D-FF 2 / Q DFF 2
r2839.0 BO: NOT-Q D-FF 2 / NOTQ DFF 2
p2840[0...1] BI: RS-FF 1 / RSFF 1
r2841.0 BO: Q RS-FF 1 / Q RSFF 1
r2842.0 BO: NOT-Q RS-FF 1 / NOTQ RSFF 1
p2843[0...1] BI: RS-FF 2 / RSFF 2
r2844.0 BO: Q RS-FF 2 / Q RSFF 2
r2845.0 BO: NOT-Q RS-FF 2 / NOTQ RSFF 2
p2846[0...1] BI: RS-FF 3 / RSFF 3
r2847.0 BO: Q RS-FF 3 / Q RSFF 3
r2848.0 BO: NOT-Q RS-FF 3 / NOTQ RSFF 3
p2849 BI: Timer 1 / Timer 1
p2850 Delay time of timer 1 / Delay time timer 1
p2851 Mode timer 1 / Mode timer 1
r2852.0 BO: Timer 1 / Timer 1
r2853.0 BO: Nout timer 1 / Nout timer 1
p2854 BI: Timer 2 / Timer 2
p2855 Delay time of timer 2 / Delay time timer 2
p2856 Mode timer 2 / Mode timer 2
r2857.0 BO: Timer 2 / Timer 2
r2858.0 BO: Nout timer 2 / Nout timer 2
p2859 BI: Timer 3 / Timer 3
p2860 Delay time of timer 3 / Delay time timer 3
p2861 Mode timer 3 / Mode timer 3
r2862.0 BO: Timer 3 / Timer 3
r2863.0 BO: Nout timer 3 / Nout timer 3
p2864 BI: Timer 4 / Timer 4
p2865 Delay time of timer 4 / Delay time timer 4
p2866 Mode timer 4 / Mode timer 4
r2867.0 BO: Timer 4 / Timer 4
r2868.0 BO: Nout timer 4 / Nout timer 4
p2869[0...1] CI: ADD 1 / ADD 1
r2870 CO: ADD 1 / ADD 1
p2871[0...1] CI: ADD 2 / ADD 2
r2872 CO: ADD 2 / ADD 2
p2873[0...1] CI: SUB 1 / SUB 1
r2874 CO: SUB 1 / SUB 1
p2875[0...1] CI: SUB 2 / SUB 2
r2876 CO: SUB 2 / SUB 2
p2877[0...1] CI: MUL 1 / MUL 1
r2878 CO: MUL 1 / MUL 1
p2879[0...1] CI: MUL 2 / MUL 2
r2880 CO: MUL 2 / MUL 2
p2881[0...1] CI: DIV 1 / DIV 1
r2882 CO: DIV 1 / DIV 1
p2883[0...1] CI: DIV 2 / DIV 2
r2884 CO: DIV 2 / DIV 2
p2885[0...1] CI: CMP 1 / CMP 1
r2886.0 BO: CMP 1 / CMP 1
p2887[0...1] CI: CMP 2 / CMP 2
r2888.0 BO: CMP 2 / CMP 2
p2889 CO: Fixed setpoint 1 in [%] / Fixed setp 1 %
p2890 CO: Fixed setpoint 2 in [%] / Fixed setp 2 %
p2940 BI: Release Wobble function / Rel Wobble
p2945 Wobble signal frequency / Wobble sig freq
p2946 Wobble signal amplitude / Wobble sig amp
p2947 Wobble signal decrement step / Signal dec step
p2948 Wobble signal increment step / Signal inc step
p2949 Wobble signal pulse width / Wobble pul width
r2955 CO: Wobble signal output / Wobble output
r3113.0...15 CO/BO: Fault Bit Array / Fault Bit Array
p3900 End of quick commissioning / Quick commiss. end
p3900 End of quick commissioning / Quick commiss. end
r3930[0...4] PS Data version / PS Data version
p3950 Access of hidden parameters / Access hidden par
r3954[0...12] CM info and GUI ID / CC info GUI ID
r3955 Version for DriveMonitor / DriveMon. version
r3978 BICO counter / BICO counter
p3981 Reset active fault / Reset active fault
p3984 Client telegram off time / Client tel. off ti
r3986[0...1] Number of parameters / No. of parameters
p7841[0...5] PM serial no hot swap check / PM Serialno
p7844 Acceptance Test, Confirmation / Ack Accept. Test
p8458 Clone Control / Clone Control
p8840 Fieldbus Off-time / FB offtime
p8841[0...15] Fieldbus configuration data / FB conf data
r8849[0...15] Fieldbus rev configuration data / FB rev conf data
r8850[0...7] CO: PZD from Fieldbus / PZD from FB
p8851[0...7] CI: PZD to Fieldbus / PZD to FB
r8858[0...15] Fieldbus diagnostic data display / FB diag data displ
r8859[0...7] Fieldbus identification data display / FB id data display
r8890.0...15 BO: Control word 1 from Fieldbus / CtrlWd1 < FB
r8891.0...15 BO: Control word 2 from Fieldbus / CtrlWd2 < FB
r8891.0...15 BO: Control word 2 from Fieldbus / CtrlWd2 < FB
p9601 SI enable parameter / SI enable
p9602 SI enable safe brake monitoring / SI brake mon. ena
p9603 SI Selection of Safety Source / SI Source select
p9650 SI Safe Digital Input debounce delay time / SI Debounce FDI
p9651 SI Safe Digital Input filter delay time / SI Filt. delay FDI
p9659 SI max time until forced dynam. / SI forc dynam time
r9660 CO: SI remain time until forc dynam / SI remaining time
p9680 SI braking ramp delay / SI braking delay
p9681 SI braking ramp down time / SI braking down ti
p9682 SI minimum frequency for standstill detection / SI min standstill
p9690 SI setpoint for SLS / SI setpoint SLS
p9691 SI tolerance for SLS / SI tolerance SLS
p9692 SI response to selecting SLS / SI SLS response
r9760 SI internal password / SI intern password
p9761 SI input password / SI input password
p9762 SI change password / SI change password
p9763 SI change password confirmation / SI passwd. confirm
r9770[0...5] SI Firmware version / SI FW version
r9771.0...1 CO/BO: SI hardware functions / SI hw functions
r9772.0...15 CO/BO: SI status word / SI StatWd
r9798 SI display checksum / SI act. checksum
p9799 SI parameter checksum / SI checksum
p9801 SI enable parameter / SI enable param.
p9802 SI enable safe brake monitoring / SI brake mon. ena
p9803 SI Selection of Safety Source / SI Source select
p9810 PROFIsafe destination address / F dest address
p9850 SI Safe Digital Input debounce delay time / SI Debounce FDI
p9851 SI Safe Digital Input filter delay time / SI Filt. time FDI
p9880 SI braking ramp delay / SI braking delay
p9881 SI braking ramp down time / SI ramp down time
p9882 SI minimum frequency for standstill detection / SI min standstill
p9890 SI setpoint for SLS / SI setpoint SLS
p9891 SI tolerance for SLS / SI tolerance SLS
p9892 SI response to selecting SLS / SI SLS response
r9898 SI display checksum / SI act. checksum
p9899 SI parameter checksum / SI checksum
r61000[0...239] PROFInet Name Of Station / PN name of station
r61001[0...3] PROFInet IP Of Station / PN IP adr
r61002[0...5] PROFInet MAC Of Station / PN MAC adr
r61003[0...3] PROFInet Default Gateway Of Station / PN Gateway adr
r61004[0...3] PROFInet Subnet Mask Of Station / PN Subnet Mask
1.3 Command and Drive Data Sets - Overview
1.3.1 Command Data Sets (CDS)
1.3.2 Drive Data Sets (DDS)
1.4 Connector/Binector (BICO)-Parameters
1.4.1 Binector Input Parameters
1.4.2 Connector Input Parameters
1.4.3 Binector Output Parameters
1.4.4 Connector Output Parameters
1.4.5 Connector/Binector Output Parameters
1.5 Quick commissioning (P0010 = 1)
2 Function diagrams
2.1 Contents: function diagrams
2.2 Symbols in function diagrams
Fig. 2-1 0010 - Symbols in function diagrams
2.3 Overview
Fig. 2-2 1100 - General Overview
Fig. 2-3 1200 - Connection of External and Internal Setpoints
2.4 External Interfaces
Fig. 2-4 2000 - Digital Inputs (DI)
Fig. 2-5 2100 - Digital Outputs (DO)
Fig. 2-6 2200 - Analog Input (AI)
Fig. 2-7 2300 - Analog Output (AO)
Fig. 2-8 2400 - Basic Operator Panel (BOP)
Fig. 2-9 2500 - USS on RS232, Receiving
Fig. 2-10 2510 - USS on RS232, Transmitting
Fig. 2-11 2600 - USS on RS485, Receiving
Fig. 2-12 2610 - USS on RS485, Transmitting
Fig. 2-13 2700 - Fieldbus, Receiving
Fig. 2-14 2710 - Fieldbus, Transmitting
Fig. 2-15 2800 - Encoder evaluation
2.5 Internal Setpoint Source
Fig. 2-16 3100 - Motor Potentiometer (MOP)
Fig. 2-17 3200 - Fixed Frequency (FF) Direct Selection (P1016 = 1)
Fig. 2-18 3210 - Fixed Frequency (FF) Binary Selection (P1016 = 2)
Fig. 2-19 3300 - Fixed PID setpoint, Direct Selection (P2216 = 1)
Fig. 2-20 3310 - Fixed PID setpoint, Binary Selection (P2216 = 2)
Fig. 2-21 3400 - PID Motor Potentiometer (PID-MOP)
2.6 Technology Functions
Fig. 2-22 4100 - Monitoring (r2197, bits 00 - 04)
Fig. 2-23 4110 - Monitoring (r2197, bits 05 - 12)
Fig. 2-24 4115 - Monitoring (r2197, bits 09 - 10) (only PM240)
Fig. 2-25 4120 - Monitoring (r2198, bits 00 - 03)
Fig. 2-26 4130 - Monitoring (r2198, bits 04 - 08)
Fig. 2-27 4140 - Monitoring (r2198, bits 09 - 12)
Fig. 2-28 4150 - Control word 1 (r0054)
Fig. 2-29 4160 - Control word 2 (r0055)
Fig. 2-30 4170 - Status word 1 (r0052)
Fig. 2-31 4180 - Status word 2 (r0053)
Fig. 2-32 4600 - Vdc Control (max, min)
2.7 Free Function Blocks
Fig. 2-33 4800 - AND-, OR-, XOR- and NOT- Elements
Fig. 2-34 4810 - FlipFlops
Fig. 2-35 4820 - Timers
Fig. 2-36 4830 - Adders, Subtracters, Multipliers, Dividers, Comparators, Setting in %
2.8 Setpoint Channel
Fig. 2-37 5000 - Setpoint channel and Motor control
Fig. 2-38 5100 - PID Controller
Fig. 2-39 5150 - Wobble Generator
Fig. 2-40 5200 - Additional Frequency Modifications (AFM)
Fig. 2-41 5300 - Ramp Function Generator
2.9 V/f Control
Fig. 2-42 6100 - Overview of V/f Control for inverters with PM240
Fig. 2-43 6200 - Overview of V/f Control for inverters with PM250/PM260
2.10 Vector Control
Fig. 2-44 7000 - Overview of Speed Control without Encoder (SLVC): P1300 = 20 & P1501 = 0
Fig. 2-45 7010 - Overview of Speed Control with Encoder (VC): P1300 = 21 & P1501 = 0
Fig. 2-46 7200 - Overview of Torque Control without Encoder (SLVC): P1300 = 22/20 & P1501 = 1
Fig. 2-47 7210 - Overview of Torque Control with Encoder (VC): P1300 = 23/21 & P1501 = 1
Fig. 2-48 7500 - Speed Controller without Encoder (SLVC): P1300 = 20 & P1501 = 0
Fig. 2-49 7510 - Speed Controller with Encoder (VC): P1300 = 21 & P1501 = 0
Fig. 2-50 7700 - Torque Control and Torque Limitation without Encoder (SLVC)
Fig. 2-51 7710 - Torque Control and Torque Limitation with Encoder (VC)
Fig. 2-52 7800 - Flux Setpoint (SLVC and VC)
Fig. 2-53 7900 - Current Controller & Observer Model without Encoder (SLVC)
Fig. 2-54 7910 - Current Controller & Observer Model with Encoder (VC)
Fig. 2-55 8000 - Analog outputs and display values
3 Faults and Alarms
3.1 Faults and Alarms - Overview
3.2 List of Fault and Alarm messages
F00001 (N) Overcurrent
F00002 Overvoltage
F00003 Undervoltage
F00004 Inverter Over Temperature
F00005 Inverter I2T
F00006 Chip temperature rise exceeds critical levels.
F00011 Motor Over Temperature
F00015 Motor temperature signal lost
F00020 Mains Phase Missing
F00021 Earth fault
F00022 Powerstack fault
F00023 Output phase fault
F00025 F3E Dclink Ripple
F00026 Supply to Gate Driver Not Enabled
F00027 Overcurrent on W phase
F00028 Power limit exceeded during regeneration
F00029 EM brake overcurrent
F00035 Auto restart after n
F00041 Motor Data Identification Failure
F00042 Speed Control Optimisation Failure
F00051 Parameter EEPROM Fault
F00052 power stack Fault
F00055 BOP-EEPROM Fault
F00056 BOP not fitted
F00057 BOP fault
F00058 BOP contents incompatible
F00060 Asic Timeout
F00061 Par Cl. MMC-PS not fitted Fault
F00062 Par Cl. MMC-PS contents invalid
F00063 Par Cl. MMC-PS contents incompatible
F00064 Drive attempted to do an automatic clone during startup
F00070 PLC setpoint fault
F00071 USS setpoint fault
F00072 USS Setpoint Fault
F00073 Control Panel setpoint fault
F00080 AI lost Input Signal
F00085 External Fault
F00090 Encoder feedback loss
F00100 Watchdog Reset
F00101 (N) Stack Overflow
F00221 PID Feedback below min. Value
F00222 PID Feedback above max. Value
F00350 Configuration vector for the drive failed
F00395 Acceptance Test / Confirmation pending
F00400 (N) PROFIBUS: DS101/DB101 (control pannel) failure
F00401 (N) Wrong telegram configured in p0922.
F00452 Belt Failure
F00453 Motor Stalled
A00501 Current Limit
A00502 Overvoltage limit
A00503 UnderVoltage Limit
A00504 Inverter OverTemperature
A00505 Inverter I2T
A00506 IGBT junction temperature rise warning
A00507 Inverter temp. signal lost
A00511 Motor OverTemperature I2T
A00523 Output fault
A00525 F3E Dclink Ripple
A00535 Braking Resistor Overload
A00541 Motor Data Identification Active
A00542 Speed Control Optimisation Active
A00544 Speed deviation
A00564 MMC Plugged During Operation
A00590 Encoder feedback loss warning
A00600 RTOS Overrun Warning
A00700 PROFIBUS: Parameter or configuration error
A00701 PROFIBUS: DoubleWord error
A00702 PROFIBUS: no bus detection
A00703 PROFIBUS: no reference values
A00704 PROFIBUS: loose of links
A00705 PROFIBUS: timeout actual value
A00706 PROFIBUS: fatal SW error (e.g. hardware check, communication, V
A00707 PROFIBUS: wrong PB address at startup
A00708 --- not used ---
A00709 --- not used ---
A00710 CB communication error
A00711 CB configuration error
A00910 Vdc-max controller de-activated
A00911 Vdc-max controller active
A00912 Vdc-min Controller active
A00921 AO parameters not set properly
A00922 No load applied to inverter
A00923 Both JOG Left and JOG Right are requested
A00936 PID Autotuning Active
A00952 Belt Failure Detected
F01600 passivated STO with drive fault
F01601 System startup error
F01610 EEPROM inconsistent
F01611 Defect in cross comparis
F01612 Diff. in hardw. detection
F01613 Maximum frequency exceeded
F01614 Frequency consistency fault
F01615 Error in hardw. environm
F01616 Processor selftest faulty
F01625 Consecutive no. incorr
F01630 Safe Brake Control faulty
F01640 PROFIsafe Driver Fault
F01649 Internal software error
F01650 Fault in safety parametr
F01655 Fault at processor reset
F01659 Denial of paramet. change
F01660 Wrong safety checksum
A01690 Safety parameter changed
A01691 SLS signal inconsistency
A01692 Speed for SLS exceeded
A01696 Switch-on is inhibited
A01697 Wrong safety param. data
A01698 Safety commis./reset act
A01699 Forced dynamis. required
A ASCII-Table
B List of Abbreviations
C Index
Parameter Manual · Edition 10/2007 Control Units CU240E CU240S sinamicsG120 G120 s
s SINAMICS SINAMICS G120 Control Units CU240E CU240S Parameter Manual Parameters Function diagrams Faults and Alarms ASCII-Table List of Abbreviations Index 1 2 3 A B C This Parameter Manual is valid for the following Control Units and Firmware versions: Control Unit CU240E CU240S CU240S DP CU240S DP-F CU240S PN CU240S PN-F As from Firmware version: V3.1 V3.0 V3.0 V3.0 V3.1 V3.1 Edition 10/2007 A5E00807461B AD
Safety Guidelines This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. Danger indicates that death or severe personal injury will result if proper precautions are not taken. Warning indicates that death or severe personal injury may result if proper precautions are not taken. Caution with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken. Caution without a safety alert symbol, indicates that property damage can result if proper precautions are not taken. Notice indicates that an unintended result or situation can occur if the corresponding information is not taken into account. If more than one degree of danger is present, the warning notice representing the highest degree of dan- ger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The device/system may only be set up and used in conjunction with this documentation. Commissioning and operation of a device/system may only be performed by qualified personnel. Within the context of the safety notes in this documentation qualified persons are defined as persons who are authorized to commission, ground and label devices, systems and circuits in accordance with established safety prac- tices and standards. Prescribed Usage Note the following: Warning This device may only be used for the applications described in the catalog or the technical description and only in connection with devices or components from other manufacturers which have been approved or recommended by Siemens. Correct, reliable operation of the product requires proper transport, storage, positioning and assembly as well as careful operation and maintenance. Trademarks All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Copyright Siemens AG 2007 All Rights Reserved Disclaimer of Liability The distribution and duplication of this document or the utilization and transmission of its contents are not permitted without express written permission. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved. Siemens AG Automation & Drives Standard Drives Postfach 3269, 91050 Erlangen Germany Siemens Aktiengesellschaft We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. © Siemens AG 2007 Technical data subject to change. SINAMICS G120 Control Units CU240E/S
Contents 1 2 3 A B C Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Introduction to Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 1.2 List of Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Command and Drive Data Sets – Overview . . . . . . . . . . . . . . . . . . . . . 1.3 Command Data Sets (CDS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3.1 1.3.2 Drive Data Sets (DDS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connector/Binector (BICO)-Parameters . . . . . . . . . . . . . . . . . . . . . . . . 1.4 Binector Input Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4.1 Connector Input Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4.2 1.4.3 Binector Output Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connector Output Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.4.4 Connector/Binector Output Parameters . . . . . . . . . . . . . . . . . . . . . . . . 1.4.5 1.5 Quick commissioning (P0010 = 1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . Function diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Contents: function diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1 2.2 Symbols in function diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.3 External Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.4 2.5 Internal Setpoint Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technology Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.6 Free Function Blocks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.7 Setpoint Channel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.8 2.9 V/f Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Vector Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.10 Faults and Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Faults and Alarms – Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.1 3.2 List of Fault and Alarm messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7 1-8 1-13 1-290 1-290 1-292 1-297 1-297 1-299 1-300 1-301 1-304 1-305 2-307 2-308 2-310 2-312 2-315 2-328 2-335 2-347 2-352 2-358 2-361 3-375 3-376 3-377 ASCII-Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-403 List of Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-405 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-411 © Siemens AG 2007 All Rights Reserved SINAMICS G120 Control Units CU240E/S, Edition 10/2007 Contents-5
Contents Contents-6 © Siemens AG 2007 All Rights Reserved SINAMICS G120 Control Units CU240E/S, Edition 10/2007
Parameters Contents 1.1 1.2 1.3 1.4 Introduction to Parameters List of Parameters Command and Drive Data Sets – Overview Connector/Binector (BICO)-Parameters 1.5 Quick commissioning (P0010 = 1) 1 1-8 1-13 1-290 1-297 1-305 © Siemens AG 2007 All Rights Reserved SINAMICS G120 Control Units CU240E/S, Edition 10/2007 1-7
Parameters Introduction to Parameters 1.1 Introduction to Parameters The layout of the parameter description is as follows. leseparameter.pdf Fig. 1-1 Read-only parameter Fig. 1-2 Write parameter schreibparameter.pdf Parameter number Indicates the relevant parameter number. The numbers used are 4-digit numbers in the range 0000 to 9999. Only for PROFINET there are a few parameters in the range of 61.000. Numbers prefixed with an “r” indicate that the parameter is a “read-only” parameter, which displays a particular value but cannot be changed directly by specifying a different value via this parameter number. All other parameters are prefixed with a “P”. The values of these parameters can be changed directly in the range indicated by the “Min” and “Max” settings in the header. If these values have a physical unit, it is shown in brackets. [index] indicates that the parameter is an indexed parameter and specifies the range of indices available. .0...15 indicates that the parameter has several bits, which can be evaluated or connected individually. 1-8 © Siemens AG 2007 All Rights Reserved SINAMICS G120 Control Units CU240E/S, Edition 10/2007